Features

  • Digital True RMS Current Meter
  • Remote Total Power Monitoring by Meter, Web, SNMP, Free Bundle Software
  • Http, Https, SNMP, DHCP, UDP
  • Individual Outlet Control
  • Power On/Off Sequence can be Defined
  • User-Defined Alarm Thresholds for Warning and Overload
  • Email, Trap, Audible Alarm

 

EJ-SWV3223C-16N2 Outlet Switched PDU 230V/32A 16 Specifications 

EJ-SWV3223C-16N2 Outlet Switched PDU 230V/32A 16 allows you to remotely control the power to your servers and other devices. The remote outlet level controls let you reboot locked-up equipment and avoid unauthorized use of individual outlets. With the power sequencing delays feature, users can control the order in which attached equipment is powered up or down and prioritize the load shedding to avoid circuit overload during power recovery.

PDU LABELS 12

 

 

General
Output(14) IEC320 C13
(2) IEC320 C19
Input(1) IEC320 309 attached power cord, 3 meters long
Protection(2) 16 AMP Circuit Breaker
Communication
SSL Indication(1) Yellow LED
DHCP Indication(1) Green LED
Circuit Status(2) Red LED
Output Status(16) Green LED
Network(1) RJ45 for Ethernet
Temp./Humidity(1) RJ11 for ENV probe connection
PDU ID1 Digits Seven Segment for PDU Identification
Current Meter3 Digits Seven Segments for True RMS Meter
Range: 0A ~ 20 A
Resolution: 0.1A
Precision: +/-2%+/-0.1AMP
Operation
Nominal Voltage230V
Voltage200V~240V full range
Frequency50/60HZ full range
Max. Output Current32 Amp
Temperature0 ~ 40 Celsius degree
Humidity0% ~ 90%
Size56 x 1245 x 44 mm
Weight4 kg

 

Regulatory
Approvals
CE, EN 55022 Class A, EN 55024,EN 61000-3-2,EN 61000-3-3
C-Tick AS/NZS CISPR 22: 2006
FCC Part 15 Class A, ICES-003
CE4